Signal Converters

Search Our Site

Logo PT. Indo Mandiri Sentosa

WSPF-DE - High-speed Response Isolator

This compact plug-in, high-speed response type converter (isolator) provides signal output which is mutually isolated between input, output and power-supply.
It amplifies and converts various kinds of signal with isolation to use in the integrated instrumental control system. It is highly effective as noise countermeasures.

Features:

  • High-speed response time 120μs
  • Fine zero & span adjustment by 15 turn trimmer
  • Zero & span adjustment ±10% full scale
  • Safe design by dielectric strength of 3000Vac
  • Compatible with 30Vdc power supply voltage
  • 5 years warranty, long life
  • CE approved

Common Specifications

Input Signal : DC current / voltage
Output Signal : DC current / voltage
Accuracy : ±0.1% FS (at 23°C)
Response time : Approx. 120μs (0 to 90%)
Allowable load : Current output
    15V or less of voltage drop between output terminal
  Voltage output
    Load current 5mA or less
      *1μA or less if the output is less than 1V FS
Zero & span adjustment : ±10% FS (15 turn trimmer)
Operating temperature : -5 to +55°C
Operating relative humidity : 90% or less (Non-condensing)
Storage temperature range : -10 to +60°C
Temperature coefficient : ±0.015% FS of span per °C
Isolation : Between input, output, and power supply
Insulation Resistance : 100MΩ or more with 500Vdc megger
  Between input, output, and power supply terminal
Dielectric Strength : 3000Vac for 1 minute between power supply and
  input/output terminal,
  2000Vac for 1 minute between input and output terminal
Power Consumption : Approx. 4.5VA (AC), Approx. 60mA (DC)
Power supply variation : ±0.1% FS (within the range of rated voltage)
Dimensions : 84(H) X 23(W) X 106.5(D)mm
Weight : Approx. 130g
Structure : Plug-in (Body part and socket part)
Connection : M3 SEMS screw part of the base socket (Tightening torque 0.6N·m)
Mounting : DIN rail or wall surface
Case color and material : Ivory, ABS resin, flame retardant grade UL94V-0
EMC directive : EN61326-1, EN61010-1, EN50581
  Installation category : II, Pollution degree : 2
Rated altitude : 2000m or less

Download Data Sheet
Download Data Sheet